IOM-7588 REV. B 12541 Ref. 97288 1 January 2, 2012 Installation, Operation and Maintenance Manual for In-Line Deflagration Flame Arrester /
IOM-7588 REV. B 12541 Ref. 97288 2Table of Contents Section Page Introduction 2 Certification 2 Integrated temperature sensors 2 Design & Functi
IOM-7588 REV. B 12541 Ref. 97288 3 *Each temperature sensor with respect to connection size has a trigger emergency function within half of the bur
IOM-7588 REV. B 12541 Ref. 97288 44. The piping system in which the deflagration arrester is to be installed must not exceed the arrester flange siz
IOM-7588 REV. B 12541 Ref. 97288 512” (300mm) 140 [190] 170 [231] (Torque is an average value based on a nitrile binder synthetic gasket, 1/32"
IOM-7588 REV. B 12541 Ref. 97288 6damaged, it should be replaced immediately with a new one. 5. Verify that the element openings are not obstructed
7The table below is a partial list of vapors for which the MESG has been measured and found to be greater than or equal to 0.045" [1.14 mm]. If